Copper conductor classes explained (IEC 60228)

The conductor inside a cable is described by a class from IEC 60228. The standard sets the maximum d.c. resistance for each conductor size, for plain copper, metal-coated (tinned) copper and aluminium.

The four classes

Class Cross-section Conductor
Class 1 Solid. A single wire.
Fixed installation
Class 2 Stranded. A few thicker wires.
Fixed installation
Class 5 Flexible. Many fine wires.
Cords, portable equipment, machines
Class 6 Extra flexible. Even more, finer wires.
Constant movement, tight bends

Drawings show the same nominal size in each class. Wire counts are illustrative; IEC 60228 limits the maximum wire diameter for classes 5 and 6 rather than fixing the number of wires.

Same size, different resistance

Classes 1 and 2 share the same maximum resistance for each size, and so do classes 5 and 6. The flexible classes are allowed a slightly higher resistance, because fine stranding packs less copper into the same nominal size.

Size (plain copper, 20°C) Class 1 and 2 Class 5 and 6
1.5 mm² 12.1 Ω/km 13.3 Ω/km
2.5 mm² 7.41 Ω/km 7.98 Ω/km

So two cables sold as 2.5 mm² can differ in resistance depending on their conductor class. Check the class when you size a cable for voltage drop.

Reading the class from a cable code

In harmonised cable codes the letter after the dash gives the conductor type: -U solid (class 1), -R stranded (class 2), -K flexible for fixed installation (class 5), -F flexible (class 5) and -H highly flexible (class 6). H07RN-F, H05VV-F and H07V-K in the Goldberg range all use class 5 conductors, as does NSHTÖU-O/J.

Need a cable for a particular bend radius or amount of movement? Ask our team and we'll recommend the right conductor.